6 Visualizing Signals TAC Xenta Server – Gateway, Technical Manual
52 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
7 In the properties pane, in the description box for the ComsFail_2
shortcut, type “PM710 is offline or incorrectly addressed” and in
the description box for the online_2 shortcut, type “PM710 is
online”.
In the Xenta 913, after sending the project, the values page appears as
follows.
Note
The text displayed in the Name column of a value is taken from
the Description property of the signal’s shortcut in XBuilder. If
no text is present in the Description box of the signal when you
drag the signal to the values page, the signal’s name is automati-
cally copied into the description of the shortcut.