4 Configuring Modbus Communication TAC Xenta Server – Gateway, Technical Manual
36 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
4.1 Adding a Modbus Master Interface
4.1.1 Adding a Modbus Master Interface
You enable the serial communication on the RS-485 A port on the
Xenta 913 by adding a communications interface in your XBuilder
project, in the example, a Modbus Master interface.
To add a Modbus Master interface
1 In XBuilder, in the network pane, right-click RS232-485 A.
2 Point to Add, point to Interface, and then click Modbus Master.
3 Type the name of the Modbus Master interface. In the example,
“Modbus_Master”.
4 In the properties pane, under Link, in the Baud Rate list, ensure
that the baud rate for the Modbus interface is correct. In the exam-
ple, 9600.